AEOLIPILE

Closed-form calculators

19 formulas. Each one says what it leaves out.

An input outside its physical range is refused with code -3, and a value that is not a finite number with code -2. Nothing is clamped. The values shown are for the default inputs and update as you type.

Generation and thermodynamics

Limits and cost arithmetic for generating plant.

Carnot efficiency limit

eta = 1 - Tc / Th, temperatures in kelvin

Does not cover. Gives the reversible upper bound only; it does not model any real cycle loss.

Maximum efficiency 0.6443 ratio

Ideal Brayton cycle efficiency

eta = 1 - pressure_ratio^(-(gamma - 1) / gamma)

Does not cover. Assumes an ideal gas with constant gamma and loss-free compression and expansion; it does not model component efficiencies, pressure drops, firing temperature limits or recuperation.

Ideal cycle efficiency 0.5621 ratio

Heat rate to efficiency

eta = 3412.142 / heat_rate; fuel = heat_rate / 1000, heat rate in Btu/kWh

Does not cover. Converts a heat rate to efficiency on whichever heating-value basis the heat rate was stated; it does not convert between higher and lower heating value or correct for part load, ambient conditions or degradation.

Efficiency 0.5018 ratio
Fuel per unit of electricity 6.8 MMBtu/MWh

Capital recovery factor

crf = r * (1 + r)^n / ((1 + r)^n - 1); crf = 1 / n when r = 0

Does not cover. Annualises one up-front cost at a single constant rate with end-of-year payments; it does not model taxes, depreciation, inflation, staged spending or salvage value.

Capital recovery factor 0.085811 1/yr

Simple levelised cost of energy

lcoe = (capex * crf + fixed_om) / (capacity_factor * 8760) * 1000 + fuel + var_om, in USD/MWh

Does not cover. Assumes constant annual output and flat costs at one discount rate; it does not include taxes, financing structure, construction interest, degradation, escalation, curtailment or decommissioning.

Levelised cost of energy 53.52 USD/MWh

PV cell temperature derate

t_cell = ambient + (noct - 20) / 800 * irradiance; derate = 1 + gamma * (t_cell - 25); p = p_stc * irradiance / 1000 * derate

Does not cover. Uses the steady-state NOCT cell temperature model with a linear power coefficient; it does not model wind cooling, mounting, spectrum, angle of incidence, soiling or inverter clipping.

Cell temperature 50 degC
DC power 72 kW
Temperature derate 0.9 ratio

Wind rotor power and Betz limit

p = 0.5 * rho * pi * (d / 2)^2 * v^3 * cp; the Betz limit is cp = 16 / 27

Does not cover. Gives rotor power at one steady wind speed and a fixed power coefficient; it does not model cut-in, rated or cut-out limits, shear, turbulence, wakes or drivetrain losses.

Rotor power 4,870.7 kW
Power at the Betz limit 6,414.1 kW

Grid and power flow

First-order grid checks. None of these is a power-flow solver.

Swing equation RoCoF

rocof = delta_p * f0 / (2 * H * S); seconds_to_floor = (f0 - f_floor) / rocof

Does not cover. Gives the initial rate of change of one aggregated machine and a straight-line time to the floor; it does not model governor or fast frequency response, load damping or regional frequency differences.

Initial rate of change of frequency 0.15 Hz/s
Time to floor at that rate 4.67 s

Per-unit base quantities

z_base = kV^2 / MVA; i_base = MVA * 1000 / (sqrt(3) * kV), kV line-to-line

Does not cover. Derives three-phase base impedance and current at one voltage level; it does not convert impedances between bases or across transformer ratios.

Base impedance 529 ohm
Base current 251 A

Three-phase line loss

i = P * 1000 / (sqrt(3) * V * pf); loss = 3 * i^2 * R / 1e6; loss_pct = loss / P * 100, P in MW and V in kV line-to-line

Does not cover. Counts series resistive loss for a balanced load at the stated voltage; it does not model charging current, corona, conductor temperature or the voltage change along the line.

Line current 264.2 A
Resistive loss 1.047 MW
Loss as a share of delivered power 1.047 %

Angle-stability transfer limit

p = v1 * v2 / x * sin(delta); p_max = v1 * v2 / x; margin_pct = (1 - p / p_max) * 100

Does not cover. Applies the lossless two-bus relation with fixed voltage magnitudes; it does not model resistance, shunt charging, thermal or voltage limits, or transient stability.

Power transfer 1,190.2 MW
Maximum transfer at 90 deg 2,380.5 MW
Margin to the maximum 50 %

N-1 loading of parallel circuits

post_loading = loading * n / (n - 1); secure when post_loading <= 100; headroom = rating * (100 - post_loading) / 100

Does not cover. Assumes identical circuits that share load equally before and after the outage; it does not model unequal impedances, the surrounding network or emergency ratings.

Loading after one outage 90 %
N-1 secure (1 yes, 0 no) 1 flag
Headroom per remaining circuit 40 MVA

Approximate voltage drop

drop_pct = (R * P + X * Q) / V^2 * 100, P in MW, Q in MVAr, V in kV line-to-line

Does not cover. Uses the linear approximation for a short series impedance at nominal voltage; it does not solve a power flow and it omits shunt charging, tap changers and the quadrature component.

Voltage drop 3.327 %

Battery, thermal and AI power

Storage, cooling and the energy cost of computation.

PUE facility load

facility = it_load * pue; overhead = it_load * (pue - 1); annual = facility * 8760

Does not cover. Holds PUE and IT load constant for all 8760 hours; it does not model seasonal cooling, partial load or on-site generation.

Facility load 65 MW
Cooling and other overhead 15 MW
Annual energy 569,400 MWh

BESS usable energy and duration

usable_out = energy * dod * sqrt(rte); duration = usable_out / power; c_rate = power / energy

Does not cover. Splits round-trip efficiency evenly between charge and discharge and holds it constant; it does not model power-dependent losses, auxiliary load, temperature or degradation.

Usable energy delivered 333.9 MWh
Duration at rated power 3.34 h
C-rate 0.25 1/h

Arrhenius acceleration factor

af = exp(Ea / k * (1 / T_ref - 1 / T_use)), k = 8.617333262e-5 eV/K, temperatures in kelvin

Does not cover. Applies one activation energy between two constant temperatures; it does not model multiple ageing mechanisms, humidity, voltage or cycling stress, and it is not a lifetime prediction.

Acceleration factor 4.341 ratio

Linear cycle fade

remaining = 100 - fade * cycles; cycles_to_eol = (100 - eol) / fade

Does not cover. Assumes capacity falls by the same amount every cycle; it does not model calendar ageing, depth of discharge, rate or temperature effects, or the knee where fade accelerates.

Remaining capacity 92 %
Cycles to end of life 5,000 cycles

Watt-to-token conversion

tokens_per_s = P_it * 1e6 * tokens_per_joule; kWh per million tokens = 1e6 / tokens_per_joule / 3.6e6, times pue at the facility

Does not cover. Converts a stated steady tokens-per-joule figure; it does not model utilisation, idle power, batch size, model choice or training energy.

Token throughput 200,000,000 tokens/s
IT energy per million tokens 0.1389 kWh/Mtok
Facility energy per million tokens 0.1806 kWh/Mtok

Coolant flow for a heat load

mass_flow = Q * 1000 / (cp * delta_t); volume_flow = mass_flow / density * 3600, Q in MW

Does not cover. Gives single-phase sensible-heat flow with constant fluid properties; it does not model phase change, pressure drop, pump power or heat-exchanger approach temperatures.

Mass flow 238.89 kg/s
Volume flow 862.6 m3/h